3051 Differential pressure transmitter
Rosemount 3051CD Differential pressure transmitter best price
Features:
±≤ 0.2% Static Accuracy
316L SST diaphragms & flanges
±≤ 0.25% stability
HART Protocol
Electrical
Power Supply :12-45 Vdc with no load
Output :4-20 mAdc linear
Zero & Span Adjust :Continuous
Warm Up: 2 seconds max
(with minimum damping)
Power Supply Effect: Less than +/-0.005% of span/volt input change
Load EffectNo effect except power across transmitter
EMI/RFI
Less than +/- 0.1% FSO;
20 to 1,000 MHz; @ 30 V/m
Performance :
Static Accuracy± 0.2% of calibrated span
Base Pressure Effect
On Zero± 0.25% FSO standard range per 2,000 psi
On Span+/-0.5% of reading for 0-30 inwc
+/- 0.25% if rdg per 1,000 psi; 0-150 inwc & 750 inwc
Temperature Effect+/- 2.5% FSO Total Error Band for 0-30 inwc
+/- 1.5% FSO Total Error Band; 0-150 inwc & 750 inwc
Vibration Effect0.05% FSO per g to 200 Hz in any axis
Mounting EffectZero shifts up to 1 inwc depending on orientation
Stability+/- 0.2% FSO per annum